Investigation of the application of IEC61850 standard in distribution busbar protection schemes
Author(s)
Mnguni, Mkhululi Elvis Siyanda
Date Issued
2013
Type
Thesis
Publisher
Cape Peninsula University of Technology
Abstract
Busbars are the most important components in the distribution networks. Faults on the busbar are uncommon, however an occurrence of a busbar fault can lead to a major loss of power. Busbars are the areas in a substation where the levels of current are high and therefore the protective relay application is very critical. In order for the protection scheme to be successful it is important to carry out the following specifications: Selectivity, Stability, Sensitivity, and Speed. To meet all of the above requirements protection must be reliable, meaning that the protection scheme must trip when called up to do so (dependability) and it must not trip when it’s not supposed to (security).
The thesis focuses on the reverse blocking busbar protection scheme with aim to improve the speed of its operation and at the same time to increase operational reliability, flexibility and stability of the protection during external and internal faults by implementation of the extended functionality provided by the IEC61850 standard-based protective IEDs. The practical implementation of the scheme by the use of IEC 61850 standard communication protocol is investigated. The research analyzes in detail the reverse blocking busbar protection scheme that is used at the moment in the power systems and it develops an improved IEC 61850 based reverse blocking busbar protection scheme for a distribution network. The proposed scheme is designed for a radial type of a distribution network and is modeled and simulated in the DigSILENT software environment for various faults on the busbar and its outgoing feeders. The results from the simulations are used further for implementation of the designed protection scheme.
A laboratory test bench is build using three compliant with the IEC 61850 standard ABB IEDs 670 series, CMC 356 Omicron test injection device, PC, MOXA switch, and a DC power supplier. Two ways of the reverse blocking signals between the IEDs implementation are considered: hard wired and Ethernet communication by using IEC 61850 standard GOOSE messages.
Comparative experimental study of the operational trip response speed of the two implementation shows that the performance of the protection scheme for the case of Ethernet communication is better
The thesis findings and deliverables will be used for postgraduate studies of other students, research, short courses, and solution of industrial problems.
Keywords: Busbar, Power system, reverse busbar blocking scheme; IEC61850; Distribution, Protection relays, IEDs, GOOSE message, laboratory test bench
The thesis focuses on the reverse blocking busbar protection scheme with aim to improve the speed of its operation and at the same time to increase operational reliability, flexibility and stability of the protection during external and internal faults by implementation of the extended functionality provided by the IEC61850 standard-based protective IEDs. The practical implementation of the scheme by the use of IEC 61850 standard communication protocol is investigated. The research analyzes in detail the reverse blocking busbar protection scheme that is used at the moment in the power systems and it develops an improved IEC 61850 based reverse blocking busbar protection scheme for a distribution network. The proposed scheme is designed for a radial type of a distribution network and is modeled and simulated in the DigSILENT software environment for various faults on the busbar and its outgoing feeders. The results from the simulations are used further for implementation of the designed protection scheme.
A laboratory test bench is build using three compliant with the IEC 61850 standard ABB IEDs 670 series, CMC 356 Omicron test injection device, PC, MOXA switch, and a DC power supplier. Two ways of the reverse blocking signals between the IEDs implementation are considered: hard wired and Ethernet communication by using IEC 61850 standard GOOSE messages.
Comparative experimental study of the operational trip response speed of the two implementation shows that the performance of the protection scheme for the case of Ethernet communication is better
The thesis findings and deliverables will be used for postgraduate studies of other students, research, short courses, and solution of industrial problems.
Keywords: Busbar, Power system, reverse busbar blocking scheme; IEC61850; Distribution, Protection relays, IEDs, GOOSE message, laboratory test bench
Additional information
Thesis (MTech (Electrical Engineering))--Cape Peninsula University of Technology, 2013